Contact information
Plot 97 Odani Road, Elelenwo Port Harcourt, Nigeria
Call: +2348036712948
fred.ebhota@rikline.net; info@rikline.net
DRILLING EQUIPMENT COMBINED SURFACE/SUBSEA LEVEL 4 R1 EXAM
Fill in your information
1 / 52
Which one of the following statements about an inside blowout preventer (IBOP) is correct?
2 / 52
What information must be included in the 'space out diagram' for the surface BOP stack?
3 / 52
What is the API Standard 53 definition of 'rated working pressure'?
4 / 52
A surface BOP stack is made up as follows (from the wellhead up):
Three ram BOPs, 13-5/8 in, 10000 psi rated working pressure.
One annular BOP, 13-5/8 in, 5000 psi rated working pressure. After the well takes a kick, the well is closed in on 5 in diameter pipe using the annular preventer.
The stabilised shut-in casing pressure (SICP) is 1000 psi.
Figure A13-0007
The graph (figure A 13-0007) shows a manufacturer's recommended closing pressures according to well pressure. Use this graph to select the 'minimum pressure range' from the options below for the annular BOP.
5 / 52
When operating a stack function from the remote BOP panel on a surface BOP installation, the open light goes out, the close light does not illuminate and the manifold pressure drops and later rises back up. Which malfunction does this indicate?
6 / 52
The well has just been shut in using the upper pipe ram.
The flow meter reads 7.2 gallons. The accumulator pressure has returned to 3000 psi. The manifold pressure has returned to 1500 psi.
Using the data in the table, has the BOP closed successfully?
7 / 52
In the diagram of a 10000-psi (10K) surface BOP stack (Figure A60-0001), why is the kill line outlet placed below the lower pipe rams?
Figure A60-0001
8 / 52
The force required to shear the pipe can be a lot greater than the force required for a pipe ram to seal around drillpipe.
What are the features of a shear ram that create the required shearing force?
9 / 52
You are drilling top-hole from a jack-up rig. An annular diverter has been installed with the flow line located above it and the overboard valves below.
Due to a shallow gas kick, you operated the diverter and the automated sequence opened both vent lines and then closed the diverter.
The wind is coming from the east. What is the next action?
10 / 52
Your rig is equipped with a Class 5-A1-R415000 psi (15K) BOP stack. What test-pump instrument and equipment rating is suitable to test this BOP?
11 / 52
On a surface BOP installation, the driller closes the pipe ram at the remote panel. The close light illuminates but the manifold pressure does not drop. What could have caused this problem?
12 / 52
The driller shuts in the well on a kick with the annular preventer on a surface BOP stack. The shut in pressures have stabilised.
The driller activates the middle pipe ram close function to protect the annular preventer.
Why is the manifold pressure reading 0 psi?
13 / 52
In which situation would you choose to do an inflow test to verify a well barrier element?
14 / 52
While circulating out a kick, pressure begins to build-up in the MGS. Why can this be dangerous?
15 / 52
When a mud gas separator (MGS) is working within its handling capability, which design feature creates the back pressure on pressure gauge 'A' (shown in Figure A41-0003)?
16 / 52
A drillpipe safety valve (DPSV) should be placed on the rig floor at all times, ready for use, to fit the tubulars in use.
Which statements are correct for this type of valve? Choose three answers.
17 / 52
A surface stack BOP has one 10000 psi (10K) rated annular preventer. Use the graph (Figure A13-0007) below to identify which well control operations can be carried out using the annular preventer. Choose two answers.
18 / 52
Figure A20-0015 shows a set of BOP remote control panel gauge readings. The BOP has not been operated and the electrically driven pump is not running. What do these gauge readings indicate?
19 / 52
Figure A20-0002 shows a set of BOP remote control panel gauge readings. The BOP has not been operated and the BOP accumulator charge pumps (electric and air) are not running. What are the possible reasons for the low accumulator pressure reading? Choose two answers.
20 / 52
Why do choke manifolds have two chokes?
21 / 52
You plan to batch-drill six top-hole sections with a diverter system which is rigged up below the rig floor. Which type of vent line will help minimise the pressure build up in the well if there is a shallow gas or water flow?
22 / 52
There is drillpipe in the hole, and you are monitoring the well on the trip tank (A63-0001). How can the BOP be configured to allow repair to the choke line remotely-controlled side outlet valve?
Figure A63-0001
23 / 52
You are planning a routine slip and cut operation with the bit at the casing shoe. Which item of equipment must be installed to make the operation safe?
24 / 52
You are tripping out of the well and are 5000 ft off bottom when the well starts to flow.
What should you do to secure the well and prepare to strip back to bottom?
25 / 52
While tripping out of the hole, the wellbore pressure-assisted annular BOP is shut in due to an influx.
If the shut-in casing pressure (SICP) is 500 psi and the manufacturer's chart recommends a minimum closing pressure of 400 psi, when would the driller adjust the closing pressure?
26 / 52
What is the main limitation of drillstring flapper valves when stripping to bottom?
27 / 52
Why is the manual valve and remotely-controlled side outlet valve installed in the position shown in the diagram (Figure A61-0001)?
Figure A61-0001
28 / 52
When a ram type BOP on a surface stack is closed, what happens to the operating fluid displaced from the opening chamber?
29 / 52
You inflow test the 7 in liner lap using a retrievable packer. The drillpipe is displaced to lightweight fluid and the packer is set above the liner lap. The BOPs are open and the annulus is monitored on the trip tank.
While reducing the drillpipe pressure by small amounts, you notice the trip tank level is decreasing. What does this indicate?
30 / 52
You are closing a pipe ram from the remote panel on a surface BOP.
The close light illuminates and the manifold pressure gauge initially drops and then returns to normal.
What causes these changes in manifold pressure?
31 / 52
How often should all operational components of the surface BOP stack equipment systems function tested according to API STD 53?
32 / 52
When testing the BOP stack with a test plug or cup type tester, why should pressure communication be maintained from below the tool to atmosphere?
33 / 52
Per API Standard 53 (2018), drillpipe safety valves (DPSVs) and inside blowout preventers (IBOPs) must be pressured tested as frequently as the BOP stack. After the BOP is installed, what test pressure should be used in the subsequent high-pressure tests?
34 / 52
What is the advantage of a self-adjusting ram lock?
35 / 52
What is the main advantage of an insert type diverter compared to a conventional large annular type of diverter?
36 / 52
You are supervising the weekly BOP function test on a surface 18-3/4 in x 10000-psi (10K) BOP stack. The regulated manifold pressure is 1500 psi and regulated annular pressure is 1000 psi. What would tell you that the annular has closed correctly?
37 / 52
What design feature do diverter systems have to minimise back-pressure on the well?
38 / 52
When circulating out a gas kick at 30 SPM, the pressure inside the mud gas separator (MGS) increases close to the maximum allowable pressure.
What should you do to reduce the risk of liquid seal loss in the MGS U-tube?
39 / 52
What is a locking device on a ram-type preventer designed to do?
40 / 52
A 15000 psi rated surface BOP stack has rams with the following closing ratios:
Which operation can be completed using 1500 psi manifold operating pressure when the BOP stack is used at full-rated working pressure?
41 / 52
A surface stack BOP consists of (from top to bottom):
1 x 10000 psi rated annular preventer 1 x 10000 psi rated 5 in - 7 in variable bore pipe ram (VBR) 1 x 10000 psi rated blind/shear rams 1 x 15000 psi rated drilling spool with 10000 psi rated remotely operated side outlet valves 1 x 10000 psi rated 5 in pipe rams
Which operation can you do with the string 3000 ft off bottom, with an influx at the bottom of the well, while keeping control of the bottomhole pressure (BHP)?
42 / 52
During a regular weekly function test of a 13-5/8 in surface stack, the supervisor records the following data. Does this stack pass its function test as per API STD 53?
43 / 52
A kick is shut in with a 10000 psi rated annular (pressure tested to 7500 psi). Rams are rated for 15000 psi.
During the pressure build-up, you decide to close the upper pipe ram due to increasing pressure.
The final stabilised shut-in casing pressure (SICP) is 10800 psi The pipe ram closing ratio is 7:1
You then decide to close the middle pipe ram. Function tests recorded a minimum of 300 psi to close the ram due to internal friction.
What is the minimum operating pressure required to close the middle ram?
44 / 52
The maximum operating pressure allowed in a mud gas separator (MGS) is often calculated assuming that there is mud in the liquid seal.
What would be the effect on this maximum operating pressure as a condensate (or oil) kick is circulated through the MGS?
45 / 52
When testing a subsea BOP stack with inverted test rams, how will the string weight affect the pressure test requirements?
46 / 52
How many SPM valves in one subsea pod move when opening the upper annular preventer?
47 / 52
When drilling ahead on a floating rig with an electro-hydraulic BOP control system, the driller tells you that the low surface accumulator pressure alarm has activated and the surface flow meter is counting rapidly. No BOP functions have been operated.
What could be the cause of the problem?
48 / 52
What is one advantage of using inverted rams during a subsea BOP test?
49 / 52
On a rig with an electro-hydraulic BOP control system, you are supervising a function test. The driller tells you that there is a problem with the upper annular BOP 'close' function. The light on the BOP panel changes to 'close' but there is no flow count or pressure drop on the annular BOP readback pressure gauge.
What could be the problem?
50 / 52
What is the purpose of having pre-charged accumulator bottles mounted on a subsea BOP stack?
Choose two answers.
51 / 52
While using the yellow pod to operate the subsea BOP Stack, the upper annular 'close' function does not operate.
The subsea engineer switches to the blue pod, and the upper-annular BOP 'close' function operates as normal.
What is the most likely cause of the yellow pod upper-annular BOP 'close' function failure?
52 / 52
What is the role of the sub-plate mounted (SPM) valve in the subsea BOP control system?
Your score is